Septic Tank Size for a 4-Bedroom House (state code tables)
The minimum septic tank for a 4-bedroom house is 1,000 to 1,500 gallons in the three states below, which publish fixed bedroom tables. Your county can require more.
Minimum tank by state
| State and rule | Minimum tank | Notes |
|---|---|---|
| Washington (WAC 246-272A-0232) | 1,000 gal | 480 gpd design flow; two compartments, first holds ½ to ⅔ |
| Pennsylvania (25 Pa. Code § 73.31) | 1,250 gal | 500 gpd design flow; 900 gal minimum for any home |
| Minnesota (Minn. R. 7080.1930) | 1,500 gal | 2,250 gal with a garbage disposal or sewage pump (+50%) |
What changes at 4 bedrooms
Four bedrooms is where the states split. Washington stays at 1,000 gallons, the last bedroom count in its first row. Pennsylvania's design flow rises to 500 gpd, so the tank jumps to 900 + 3.5 × 100 = 1,250 gallons. Minnesota moves to its 4 to 5 bedroom row at 1,500 gallons, and 2,250 with a garbage disposal.
Drain field for 4 bedrooms (Washington)
Washington sizes the drain field from design flow (480 gpd for 4 bedrooms) divided by the soil's loading rate in WAC 246-272A-0234 Table VIII. These are primary areas for ordinary septic tank effluent; a reserve area of the same size is also required. Try your own numbers in the drain field calculator.
| Washington soil type | Loading rate | Drain field area |
|---|---|---|
| Type 1 | 1.0 gal/sq ft/day | 480 sq ft |
| Type 2 | 1.0 gal/sq ft/day | 480 sq ft |
| Type 3 | 0.8 gal/sq ft/day | 600 sq ft |
| Type 4 | 0.6 gal/sq ft/day | 800 sq ft |
| Type 5 | 0.4 gal/sq ft/day | 1,200 sq ft |
| Type 6 | 0.2 gal/sq ft/day | 2,400 sq ft |
Before you buy a tank
Local health officers can require more than the state minimum; Washington's design-flow rule says so directly. Get the number from your local permit office or a licensed designer. Run other bedroom counts in the septic tank size calculator, or compare: 2 bedrooms · 3 bedrooms · 5 bedrooms.
Sources
- Washington Administrative Code 246-272A-0232, Septic tank sizing
- Washington Administrative Code 246-272A-0230, Design flow (120 gpd per bedroom, 240 gpd minimum)
- Washington Administrative Code 246-272A-0234, Soil dispersal components (Table VIII loading rates)
- 25 Pa. Code § 73.31, Standards for septic tanks
- Minnesota Rules 7080.1930, Septic tank capacity (Table V)